Danfoss FC 300 Design Manual page 129

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
kPa
m WG
Power:
kW
Flow, volume:
GPM
gal/s
gal/min
gal/h
CFM
ft
3
/s
3
ft
/min
3
ft
/h
Flow, mass:
lb/s
lb/min
lb/h
Velocity:
ft/s
ft/min
Length:
ft
Temperature:
° F
Pressure:
psi
lb/in
2
in WG
ft WG
Power:
HP
Function:
It is possible to program a value to be shown in
the display of the LCP. The value will have a linear,
squared or cubed relation to speed. This relation
will depend on the unit selected (see table above).
The actual calculated value can be read in Custom
Readout, par. 16-09, and/or shown in the display
be selecting Custom Readout [16-09] in par. 0-20
– 0-24, Display Line X.X Small (large).
0-31
Custom Readout Min Value
Value:
0 - par. 0 - 32
factory setting
How to Programme
[73]
[74]
[80]
[120]
[121]
[122]
[123]
[124]
[125]
[126]
[127]
[130]
[131]
[132]
[140]
[141]
[145]
[160]
[170]
[171]
[172]
[173]
[180]
0.00
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
Function:
This parameter allows the choice of the min. value
of the custom defined readout (occurs at zero
speed). Only possible to set different from 0 is
when selecting a linear unit in Custom Readout
Unit, par. 0-30. For Quadratic and Cubic units the
minimum value will be 0.
0-32
Custom Readout Max Value
Value:
Par. 0-31 - 999999.99
Function:
This parameter allows the choice of the value to
be shown when the speed of the motor has
reached the set value for Motor Speed High Lim-
it, (par.4-13/4-14).
0-4* LCP Keypad
Enable and disable individual keys on the LCP key-
pad.
0-40
[Hand on] Key on LCP
Value:
Disabled
Enabled
Password
Function:
Select Disabled [0] to avoid accidental start of the
frequency converter in Hand mode. Select Pass-
word [2] to avoid unauthorised start in Hand
mode. If par. 0-40 is included in the Quick Menu,
then define the password in par. 0-65 Quick Menu
Password.
0-41
[Off] Key on LCP
Value:
Disabled
Enabled
Password
Function:
Select Disabled [0] to avoid accidental stop of the
frequency converter. Select Password [2] to avoid
unauthorised stop. If par. 0-41 is included in the
Quick Menu, then define the password in par. 0-65
Quick Menu Password.
value for use in communication via serial communication port
0.00
[0]
[1]
[2]
[0]
[1]
[2]
129