FC 300 Design Guide
5-63
Terminal 29 Pulse Output Variable
Value:
No operation
Function:
Select the variable for viewing on the terminal 29
display. This parameter is available for FC 302 on-
ly.
This parameter cannot be adjusted while the mo-
tor is running.
Pulse Output Maximum Frequency
5-65
#29
Value:
0 - 32000 Hz
Function:
Set the maximum frequency for terminal 29 cor-
responding to the output variable set in par. 5-63.
This parameter cannot be adjusted while the mo-
tor is running.
Terminal X30/6 Pulse Output Vari-
5-66
able
Value:
No operation
Function:
Select the variable for read-out on terminal
X30/6. This parameter cannot be adjusted while
the motor is running.
This parameter is active when option module MCB
101 is installed in the frequency converter.
Pulse Output Maximum Frequency
5-68
#X30/6
Value:
No operation
Function:
Select the maximum frequency on terminal X30/6
referring to the output variable in par. 5-66. This
parameter cannot be adjusted while the motor is
running.
This parameter is active when option module MCB
101 is mounted in the frequency converter.
factory setting
176
How to Programme
[0]
5000Hz
[0]
[0]
()
display text
[]
value for use in communication via serial communication port
MG.33.B7.02 - VLT is a registered Danfoss trademark
5-7* 24 V Encoder Input
Parameters for configuring the 24V encoder.
Connect the 24 V encoder to terminal 12 (24 V DC
supply), terminal 32 (Channel A), terminal 33
(Channel B), and terminal 20 (GND). The digital
inputs 32/33 are active for encoder inputs when
24V encoder is selected in par. 1-02 and par.
7-00. The encoder used is a dual channel (A and
B) 24 V type. Max input frequency: 110 kHz.
5-70
Term 32/33 Pulses per Revolution
Value:
128 - 4096 PPR
Function:
Set the encoder pulses per revolution on the mo-
tor shaft. Read the correct value from the encod-
er.
This parameter cannot be adjusted while the mo-
tor is running.
5-71
Term 32/33 Encoder Direction
Value:
* Clockwise
Counter clockwise
Function:
Change the detected encoder rotation direction
without changing the wiring to the encoder. Select
1024PPR
[0]
[1]