FC 300 Design Guide
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be re-
tained at power-down.
Select Off [0] to deactivate the non-volatile stor-
age function.
Select Store edit setup [1] to store all parameter
values in the set-up selected in par. 9-70 in the
non-volatile memory. The selection returns to Off
[0] when all values have been stored.
Select Store all set-ups [2] to store all parameter
values for all set-ups in the non-volatile memory.
The selection returns to Off [0] when all parame-
ter values have been stored.
9-72
Drive Reset
Value:
No action
Power-on reset
Comm. option reset
Function:
Select Power-on reset [1] to reset the frequency
converter upon power-up, as for power-cycle.
Select Comm. option reset [3] to reset the Profi-
bus option only, useful after changing certain set-
tings in parameter group 9-**, e.g. par. 9-18.
When reset, the frequency converter disappears
from the fieldbus, which may cause a communi-
cation error from the master.
9-80
Defined Parameters (1)
Array [116]
Value:
No LCP access
Read only
0 - 115
Function:
This parameter displays a list of all the defined
frequency converter parameters available for Pro-
fibus.
factory setting
198
How to Programme
[0]
[1]
[3]
()
display text
[]
value for use in communication via serial communication port
MG.33.B7.02 - VLT is a registered Danfoss trademark
9-81
Defined Parameters (2)
Array [116]
Value:
No LCP access
Read only
0 - 115
Function:
This parameter displays a list of all the defined
frequency converter parameters available for Pro-
fibus.
9-82
Defined Parameters (3)
Array [116]
Value:
No LCP access
Read only
0 - 115
Function:
This parameter displays a list of all the defined
frequency converter parameters available for Pro-
fibus.
9-83
Defined Parameters (4)
Array [116]
Value:
No LCP access
Read only
0 - 115
Function:
This parameter displays a list of all the defined
frequency converter parameters available for Pro-
fibus.
9-84
Defined Parameters (5)
0
Value:
Array [116]
No LCP access
Read only
0 - 115
0
0
0
0