Danfoss FC 300 Design Manual page 191

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
8-35
Minimum Response Delay
Value:
1 - 500 ms
Function:
Specify the minimum delay time between receiv-
ing a request and transmitting a response. This is
used for overcoming modem turnaround delays.
8-36
Max Response Delay
Value:
1 - 10000 ms
Function:
Specify the maximum permissible delay time be-
tween transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause
control word time-out.
8-37
Max Inter-Char Delay
Value:
0 - 30 ms
Function:
Specify the maximum permissible time interval
between receipt of two bytes. This parameter ac-
tivates time-out if transmission is interrupted.
This parameter is active only when par. 8-30 is set
to FC MC [1] protocol.
8-40
FC MC Protocol Set
Value:
Standard Telegram 1
Custom Telegram
Function:
Enables use of freely configurable telegrams or
standard telegrams for the FC port.
8-5* Digital/Bus
Parameters for configuring the control word Digi-
tal/Bus merging.
8-50
Coasting Select
Value:
Digital input
Bus
Logic AND
factory setting
How to Programme
10ms
5000ms
25ms
[1]
[200]
[0]
[1]
[2]
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
Logic OR
Function:
Select control of the coasting function via the ter-
minals (digital input) and/or via the bus.
NB!
This parameter is active only when
par. 8-01 Control Site is set to [0] Dig-
ital and control word.
8-51
Quick Stop Select
Value:
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the Quick Stop function via the
terminals (digital input) and/or via the bus.
NB!
This parameter is active only when
par. 8-01 Control Site is set to [0] Dig-
ital and control word.
8-52
DC Brake Select
Value:
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site is set to [0] Dig-
ital and control word.
8-53
Start Select
Value:
Digital input
Bus
value for use in communication via serial communication port
[3]
[0]
[1]
[2]
[3]
[0]
[1]
[2]
[3]
[0]
[1]