How to Programme
P 2-03
Status
Quick
Menu
Setup
Illustration 2.24
2.1.16 Local Control Keys
Keys for local control are found at the bottom of the LCP.
Hand
O
on
Illustration 2.25
[Hand On] enables control of the frequency converter via
the LCP. [Hand On] also starts the motor and it is now
possible to enter the motor speed data by means of the
arrow keys. The key can be selected as [1] Enable or [0]
Disable via 0-40 [Hand on] Key on LCP.
External stop signals activated by means of control signals
or a serial bus will override a 'start' command via the LCP.
The following control signals are still active when [Hand
On] is activated:
•
[Hand On] - [Off] - [Auto On]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via 0-41 [Off] Key on LCP.
If no external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
voltage.
[Auto On] enables the frequency converter to be
controlled via the control terminals and/or serial communi-
cation. When a start signal is applied on the control
®
VLT
AutomationDrive Programmming Guide
Setup 1
Main
Menu
Auto
Reset
on
®
MG33ME02 - VLT
is a registered Danfoss trademark
terminals and/or the bus, the frequency converter will
start. The key can be selected as [1] Enable or [0] Disable
via 0-42 [Auto on] Key on LCP.
NOTE
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand On] [Auto On].
[Reset] is used for resetting the frequency converter after
an alarm (trip). It can be selected as [1] Enable or [0]
Disable via 0-43 [Reset] Key on LCP.
2.1.17 Initialisation to Default Settings
Initialise the frequency converter to default settings in two
ways.
Recommended initialisation (via 14-22 Operation Mode)
1.
Select 14-22 Operation Mode
2.
Press [OK]
3.
Select "Initialisation"
4.
Press [OK]
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
14-22 Operation Mode initialises all except:
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 FC Port Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-Char Delay
15-00 Operating Hours to 15-05 Over Volt's
15-20 Historic Log: Event to 15-22 Historic Log:
Time
15-30 Fault Log: Error Code to 15-32 Alarm Log:
Time
2
2
21