10-2* COS Filters
Parameters for configuring COS filter settings.
10-20
COS Filter 1
Value:
0 - FFFF
Function:
Enter the value for COS Filter 1 to set up the filter
mask for the Status Word. When operating in COS
(Change-Of-State), this function filters out bits in
the Status Word that should not be sent if they
change.
10-21
COS Filter 2
Value:
0 - FFFF
Function:
Enter the value for COS Filter 2, to set up the filter
mask for the Main Actual Value. When operating
in COS (Change-Of-State), this function filters out
bits in the Main Actual Value that should not be
sent if they change.
10-22
COS Filter 3
Value:
0 - FFFF
Function:
Enter the value for COS Filter 3, to set up the filter
mask for PCD 3. When operating in COS (Change-
Of-State), this function filters out bits in PCD 3
that should not be sent if they change.
10-23
COS Filter 4
Value:
0 - FFFF
Function:
Enter the value for COS Filter 4 to set up the filter
mask for PCD 4. When operating in COS (Change-
Of-State), this function filters out bits in PCD 4
that should not be sent if they change.
10-3* Parameter Access
Parameter group providing access to indexed pa-
rameters and defining programming set-up.
factory setting
How to Programme
0000
0000
0000
0000
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
10-30
Array Index
Value:
0 - 255
Read only from LCP.
Function:
View array parameters. This parameter is valid
only when a DeviceNet fieldbus is installed.
10-31
Store Data Values
Value:
Off
Store edit setup
Store all setups
Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be re-
tained at power-down.
Select Off [0] to deactivate the non-volatile stor-
age function.
Select Store edit setup [1] to store all parameter
values from the active set-up in the non-volatile
memory. The selection returns to Off [0] when all
values have been stored.
Select Store all set-ups [2] to store all parameter
values for all set-ups in the non-volatile memory.
The selection returns to Off [0] when all parame-
ter values have been stored.
10-32
Devicenet Revision
Value:
Major revision
Minor revision
Function:
View the DeviceNet revision number. This param-
eter is used for EDS file creation.
10-33
Store Always
Value:
Off
On
value for use in communication via serial communication port
0
[0]
[1]
[2]
[0]
[1]