1.1.16. Initialisation to Default Settings

Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1.
2.
3.
4.
5.
Par. 14-22 initialises all except:
14-50
8-30
8-31
8-32
8-35
8-36
8-37
15-00 to 15-05
15-20 to 15-22
15-30 to 15-32
Manual initialisation
Enabled
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the
control keys [Hand on] [Auto on].
[0] via par. 0-43
Reset Keys on LCP
Select par. 14-22
Press [OK]
Select "Initialisation"
Press [OK]
Cut off the mains supply and wait
until the display turns off.
NB!
Keeps parameters selected in
RFI 1
Protocol
Address
Baud Rate
Minimum Response Delay
Max Response Delay
Max Inter-char Delay
Operating data
Historic log
Fault log
®
MG.20.O2.02 - VLT
is a registered Danfoss trademark
Disabled
[1] or
[0] via par. 0-42
.
6.
Reconnect the mains supply - the
frequency converter is now reset.
7.
Change par. 14-22 back to
Operation
.
Personal Menu
with default factory setting.