FC 300 Design Guide
rated motor speed (par. 1-25). To protect the mo-
tor from reaching the stalling torque, the default
setting is 1.6 x the rated motor torque (calculated
value). If a setting in par. 1-00 to par. 1-26 is
changed, par. 4-16 to 4-18 are not automatically
reset to the default settings.
Changing par. 4-16 Torque Limit Motor
Mode when par. 1-00 is set to Speed
open loop [0], par. 1-66 Min Current at
Low Speed is automatically readjus-
ted.
4-17
Torque Limit Generator Mode
Value:
0.0 - Variable Limit %
Function:
Sets the torque limit for generator mode opera-
tion. The torque limit is active in the speed range
up to the rated motor speed (par. 1-25). See il-
lustration for par. 4-16 as well as par. 14-25 for
further details.
4-18
Current Limit
Value:
0.0 - Variable Limit %
Function:
Sets the current limit for motor operation. To pro-
tect the motor from reaching the stalling torque,
the default setting is 1.6 x the rated motor torque
(calculated value). If a setting in par. 1-00 to par.
1-26 is changed, par. 4-16 to par. 4-18 are not
automatically reset to the default settings.
4-19
Max Output Frequency
Value:
0.0 - 1000.0 Hz
factory setting
How to Programme
160.0 %
160.0 %
132.0Hz
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
Function:
Provides a final limit on the drive output frequency
for improved safety in applications where you
want to avoid accidental over-speeding. This limit
is final in all configurations (independent of the
setting in par. 1-00).
NB!
Max. output frequency cannot exceed
10% of the inverter switching frequen-
cy (par. 14-01).
Par. 4-19 cannot be adjusted while the motor is
running.
4-20
Torque Limit Factor SourceOption
Value:
No function
Analog input 53
Analog input 53 inv
Analog input 54
Analog input 54 inv
Analog input X30-11
Analog input X30-11 inv
Analog input X30-12
Analog input X30-12 inv
Function:
Select an analog input for scaling the settings in
par. 4-16 and 4-17 from 0% to 100% (or inverse).
The signal levels corresponding to 0% and 100%
are defined in the analog input scaling, e.g. par.
group 6-1*. This parameter is only active when
par. 1-00 Configuration Mode is in Speed Open
Loop or Speed Closed Loop.
4-21
Speed Limit Factor SourceOption
Value:
No function
Analog input 53
Analog input 53 inv
Analog input 54
Analog input 54 inv
Analog input X30-11
Analog input X30-11 inv
Analog input X30-12
Analog input X30-12 inv
value for use in communication via serial communication port
[0]
[2]
[4]
[6]
[8]
[10]
[12]
[14]
[16]
[0]
[2]
[4]
[6]
[8]
[10]
[12]
[14]
[16]