FC 300 Design Guide
0-42
[Auto on] Key on LCP
Value:
Disabled
Enabled
Password
Function:
Select Disabled [0] to avoid accidental start of the
frequency converter in Auto mode. Select Pass-
word [2] to avoid unauthorised start in Auto
mode. If par. 0-42 is included in the Quick Menu,
then define the password in par. 0-65 Quick Menu
Password.
0-43
[ Reset] Key on LCP
Value:
Disabled
Enabled
Password
Function:
Press [Reset] and select Disabled [0] to avoid ac-
cidental alarm reset. Press [Reset] and select
Password [2] to avoid unauthorised resetting. If
par. 0-43 is included in the Quick Menu, then de-
fine the password in par. 0-65 Quick Menu Pass-
word.
0-5* Copy / Save
Copy parameter settings between set-ups and to/
from the LCP.
0-50
LCP Copy
Value:
No copy
All to LCP
All from LCP
Size indep. from LCP
File from MCO to LCP
File from LCP to MCO
Function:
Select All to LCP [1] to copy all parameters in all
set-ups from the frequency converter memory to
the LCP memory.
factory setting
130
How to Programme
[0]
[1]
[2]
[0]
[1]
[2]
[0]
[1]
[2]
[3]
[4]
[5]
()
display text
[]
value for use in communication via serial communication port
MG.33.B7.02 - VLT is a registered Danfoss trademark
Select All from LCP all [2] to copy all parameters
in all set-ups from the LCP memory to the fre-
quency converter memory.
Select Size indep. from LCP [3] to copy only the
parameters that are independent of the motor
size. The latter selection can be used to pro-
gramme several drives with the same function
without disturbing motor data. This parameter
cannot be adjusted while the motor is running.
0-51
Set-up Copy
Value:
No copy
Copy to set-up 1
Copy to set-up 2
Copy to set-up 3
Copy to set-up 4
Copy to all
Function:
Select Copy to set-up 1 [1] to copy all parameters
in the present edit set-up (defined in par. 0-11
Edit Set-up) to Set-up 1. Likewise, select the op-
tion corresponding to the other set-up(s). Select
Copy to all [9] to copy the parameters in the
present set-up over to each of the set-ups 1 to 4.
0-6* Password
Define password access to menus.
0-60
Main Menu Password
Value:
0 - 999
Function:
Define the password for access to the Main Menu
via the [Main Menu] key. If par. 0-61 Access to
Main Menu w/o Password is set to Full access [0],
this parameter will be ignored.
Access to Main Menu w/o Pass-
0-61
word
Value:
Full access
Read only
No access
[0]
[1]
[2]
[3]
[4]
[9]
100
[0]
[1]
[2]