Danfoss FC 300 Design Manual page 225

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Digital input DI33
Comparator 4
Comparator 5
Logic rule 4
Logic rule 5
Function:
Select the trigger event. When the trigger event
occurs, a window is applied to freeze the log. The
log will then retain a specified percentage of sam-
ples before the occurrence of the trigger event
(par. 15-14).
15-13
Logging Mode
Value:
Log always
Log once on trigger
Function:
Select Log always [0] for continuous logging.
Select Log once on trigger [1] to conditionally
start and stop logging using par. 15-12 and par.
15-14.
15-14
Samples Before Trigger
Value:
0 - 100
Function:
Enter the percentage of all samples prior to a trig-
ger event which are to be retained in the log. See
also par. 15-12 and par. 15-13.
15-2* Historic Log
View up to 50 logged data items via the array pa-
rameters in this parameter group. For all param-
eters in the group, [0] is the most recent data and
[49] the oldest data. Data is logged every time an
event occurs (not to be confused with SLC
events). Events in this context are defined as a
change in one of the following areas:
1.
Digital input
2.
Digital outputs (not monitored in this SW
release)
3.
Warning word
4.
Alarm word
5.
Status word
factory setting
How to Programme
[38]
[50]
[51]
[60]
[61]
[0]
[1]
50
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
6.
Control word
7.
Extended status word
Events are logged with value, and time stamp in
msec. The time interval between two events de-
pends on how often events occur (maximum once
every scan time). Data logging is continuous but
if an alarm occurs, the log is saved and the values
can be viewed on the display. This feature is use-
ful, for example when carrying out service follow-
ing a trip. View the historic log contained in this
parameter via the serial communication port or
via the display.
15-20
Historic Log: Event
Array [50]
Value:
0 - 255
Function:
View the event type of the logged events.
15-21
Historic Log: Value
Array [50]
Value:
0 - 2147483647
Function:
View the value of the logged event. Interpret the
event values according to this table:
Digtal input
Digital output (not
monitored in this SW
release)
Warning word
Alarm word
Status word
Control word
Extended
status
word
15-22
Historic Log: Time
Array [50]
Value:
0 - 2147483647
value for use in communication via serial communication port
Decimal value. See par. 16-60 for de-
scription after converting to binary
value.
Decimal value. See par. 16-66 for de-
scription after converting to binary
value.
Decimal value. See par. 16-92 for de-
scription.
Decimal value. See par. 16-90 for de-
scription.
Decimal value. See par. 16-03 for de-
scription after converting to binary
value.
Decimal value. See par. 16-00 for de-
scription.
Decimal value. See par. 16-94 for de-
scription.
0
0
0
225