FC 300 Design Guide
Byte
Content
0 - 5
Standard DP Di-
agnose Data
6
PDU length xx
7
Status
type
0x81
8
Slot = 0
9
Status info = 0
10 - 13
VLT par. 16-92
14 - 17
VLT par. 16-03
18 - 21
VLT par. 16-90
22 - 23
VLT par. 9-53
Enabling diagnosis may cause increased bus traf-
fic. Diagnosis functions are not supported by all
fieldbus types.
8-1* Ctrl. Word Settings
Parameters for configuring the option control
word profile.
8-10
Control Word Profile
Value:
FC profile
PROFIdrive profile
ODVA
CANopen DSP 402
Function:
Select the interpretation of the control and status
words corresponding to the installed fieldbus. On-
ly the selections valid for the fieldbus installed in
slot A will be visible in the LCP display.
For guidelines in selection of FC profile [0] and
PROFIdrive profile [1] please refer to the Serial
communication via RS 485 Interface section in the
How to Programmechapter.
For additional guidelines in the selection of PRO-
FIdrive profile [1], ODVA [5] and CANopen DSP
402 [7], please refer to the Operating Instructions
for the installed fieldbus.
8-13
Configurable Status Word STW
Value:
Bit 12
Bit 13
Bit 14
Bit 15
factory setting
190
How to Programme
Description
Standard DP Diagnose Data
Header of extended diagnos-
tic data
=
Header of extended diagnos-
tic data
Header of extended diagnos-
tic data
Header of extended diagnos-
tic data
VLT warning word
VLT status word
VLT alarm word
Communication warning word
(Profibus)
[0]
[1]
[5]
[7]
[12]
[13]
[14]
[15]
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
Function:
This parameter enables configuration of bit 12 –
15 in the status word.
Profile Default [1]:
responds to the profile default selected in par.
8-10.
Alarm 68 Only [2]:
an Alarm 68.
Trip except Alarm 68 [3]:
of a trip, except if the trip is executed by an Alarm
68.
T37 DI status [16]:
of terminal 37.
"0" indicates T37 is low (safe stop)
"1" indicates T37 is high (normal)
8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30
Protocol
Value:
FC
FC MC
Function:
Select the protocol for the FC (standard) port.
8-31
Address
Value:
1 - 126
Function:
Enter the address for the FC (standard) port.
Valid range: 1 - 126.
8-32
FC Port Baud Rate
Value:
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
115200 Baud
Function:
Baud rate selection for the FC (standard) port.
value for use in communication via serial communication port
The function on the bit cor-
The bit is only set in case of
The bit is set in case
The bit indicates the status
[0]
[1]
1
[0]
[1]
[2]
[3]
[4]
[7]