FC 300 Design Guide
516 - Cannot write write to the E^2 PROM be-
cause a write command is on progress
517 - The write command is under time out 518 –
Failure in the E^2 Prom
519 - Missing or invalid BarCode data in E^2Prom
1024 – 1279 CAN telegram cannot be sent. (1027
indicate a possible hardware failure)
1281 - Digital Signal Processor flash time-out
1282 - Power micro software version mismatch
1283 - Power E^2PROM data version mismatch
1284 - Cannot read Digital Signal Processor soft-
ware version
1299 - OptionSW in slot A is too old
1300 - OptionSW in slot B is too old
1301 - OptionSW in slot C0 is too old
1302 - OptionSW in slot C1 is too old
1315 - Option SW in slot A is not supported (not
allowed)
1316 - Option SW in slot B is not supported (not
allowed)
1317 - Option SW in slot C0 is not supported (not
allowed)
1318 - Option SW in slot C1 is not supported (not
allowed)
1536 - An exception in the Application Orientated
Control is registered. Debug information written in
LCP
1792 - DSP watchdog is active. Debugging of
power part data Motor Orientated Control data not
transferred correctly
2049 - Power data restarted
2315 - Missing SW version from power unit.
2816 - Stack overflow Control board module
2817 - Scheduler slow tasks
2818 - Fast tasks
2819 - Parameter thread
2820 - LCP stack overflow
2821 - Serial port overflow
2822 - USB port overflow
3072 - 5122 Parameter value is outside its limits.
Perform a initialization. Parameter number caus-
ing the alarm: Subtract the code from 3072. Ex
Error code 3238: 3238-3072 = 166 is outside the
limit..
5123 - Option in slot A: Hardware incompatible
with Control board hardware.
5124 - Option in slot B: Hardware incompatible
with Control board hardware
5125 - Option in slot C0: Hardware incompatible
with Control board hardware
5126 - Option in slot C1: Hardware incompatible
with Control board hardware
298
Troubleshooting
5376 - 5631 Out of memory
WARNING 47
24 V supply low:
The external 24 V DC backup power supply may
be overloaded, otherwise contact your Danfoss
supplier.
ALARM 48
1.8 V supply low:
Contact your Danfoss supplier.
WARNING 49
Speed limit:
The speed has been limited by range in par. 4-11
and par. 4-13.
ALARM 50
AMA calibration failed:
Contact your Danfoss supplier.
ALARM 51
AMA check Unom and Inom:
The setting of motor voltage, motor current, and
motor power is presumably wrong. Check the set-
tings.
ALARM 52
AMA low Inom:
The motor current is too low. Check the settings.
ALARM 53
AMA motor too big:
The motor is too big for the AMA to be carried out.
ALARM 54
AMA motor too small:
The motor is too small for the AMA to be carried
out.
ALARM 55
AMA par. out of range:
The par. values found from the motor are outside
acceptable range.
ALARM 56
AMA interrupted by user:
The AMA has been interrupted by the user.
ALARM 57
AMA timeout:
Try to start the AMA once again, until the AMA is
carried out. Please note that repeated runs may
heat the motor to a level where the resistance Rs
and Rr are increased.
WARNING/ALARM 58
AMA internal fault:
Contact your Danfoss supplier.
MG.33.B7.02 - VLT is a registered Danfoss trademark