Danfoss FC 300 Design Manual page 171

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Brake fault (IGBT)
Logic '1' when the brake IGBT is short-
circuited. Use this function to protect the
frequency converter if there is a fault on
the brake modules. Use the output/relay
to cut out the main voltage from the fre-
quency converter.
Relay 123
[31]: The relay is activated
when Control Word [0] is selected in pa-
rameter group 8-**.
Mechanical brake control
bles control of an external mechanical
brake, see description in the section Con-
trol of Mechanical Brake, and par. group
2-2*
Safe stop activated
that the safe stop on terminal 37 has been
activated.
Out of ref range [40]
Below reference low [41]
Above reference high [42]
Bus Ctrl [45]
Bus Ctrl On at time-out [46]
Bus Ctrl Off at time-out [47]
MCO controlled [51]
Pulse output [55]
Comparator 0
13-1*. If Comparator 0 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Comparator 1
13-1*. If Comparator 1 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Comparator 2
13-1*. If Comparator 2 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Comparator 3
13-1*. If Comparator 3 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Comparator 4
13-1*. If Comparator 4 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
factory setting
How to Programme
[30]: The output is
[32]: Ena-
[33]: Indicates
[60]: See par. group
[61]: See par. group
[62]: See par. group
[63]: See par. group
[64]: See par. group
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
Comparator 5
13-1*. If Comparator 5 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 0
13-4*. If Logic Rule 0 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 1
13-4*. If Logic Rule 1 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 2
13-4*. If Logic Rule 2 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 3
13-4*. If Logic Rule 3 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 4
13-4*. If Logic Rule 4 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
Logic Rule 5
13-4*. If Logic Rule 5 is evaluated as
TRUE, the output will go high. Otherwise,
it will be low.
SL Digital Output A
13-52 SL Control Action. The input will go
high whenever the Smart Logic Action
[38] Set dig. out. A high is executed. The
input will go low whenever the Smart Log-
ic Action [32] Set dig. out. A low is exe-
cuted.
SL Digital Output B
13-52 SL Control Action. The input will go
high whenever the Smart Logic Action
[39] Set dig. out. A high is executed. The
input will go low whenever the Smart Log-
ic Action [33] Set dig. out. A low is exe-
cuted.
SL Digital Output C
13-52SL Control Action. The input will go
high whenever the Smart Logic Action
[40] Set dig. out. A high is executed. The
input will go low whenever the Smart Log-
ic Action [34] Set dig. out. A low is exe-
cuted.
value for use in communication via serial communication port
[65]: See par. group
[70]: See par. group
[71]: See par. group
[72]: See par. group
[73]: See par. group
[74]: See par. group
[75]: See par. group
[80]: See par.
[81]: See par.
[82]: See par.
171

Advertisement

Table of Contents
loading

Table of Contents