Set-up select lsb - Set-up select msb
Stop command from serial communication
Quick stop
DC brake
[Off]
stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. 0-41 [Off]
key on LCP. If no external stop function is selected and the [Off] key is inactive the motor can be stopped
by disconnecting the voltage.
[Auto On]
enables the frequency converter is to be controlled via the control terminals and/or serial
communication. When a start signal is applied on the control terminals and/or the bus, the frequency
converter will start. The key can be selected as Enable [1] or Disable [0] via par. 0-42 [Auto on] key on
LCP.
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control
keys [Hand on] – [Auto on].
[ Reset ]
is used for resetting the frequency converter after an alarm (trip). It can be selected as En-
able [1] or Disable [0] via par. 0-43 Reset Keys on LCP.
The parameter shortcut
parameter shortcut allows direct access to any parameter.

Quick Transfer of Parameter Settings

Once the set-up of a drive is complete, we rec-
ommend that you store the data in the LCP or on
a PC via MCT 10 Set-up Software Tool.
Data storage in LCP:
1.
Go to par. 0-50 LCP Copy
2.
Press the [OK] key
3.
Select "All to LCP"
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached,
press [OK].
NB!
Stop the motor before performing this operation.
You can now connect the LCP to another frequency converter and copy the parameter settings to this
frequency converter as well.
110
How to Programme
can be carried out by holding down the [Main Menu] key for 3 seconds. The
MG.33.B7.02 - VLT is a registered Danfoss trademark