Danfoss FC 300 Design Manual page 181

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
6-41
Term. X30/12 High Voltage
Value:
Par. 6-40 to 10.0 V
Function:
Sets the analog input scaling value to correspond
to the high reference/feedback value set in par.
6-45.
Term. X30/12 Low Ref./Feedb.
6-44
Value
Value:
-1000000.000 to par. 6-45
Function:
Sets the analog input scaling value to correspond
to the low voltage value set in par. 6-44.
Term. X30/12 High Ref./Feedb.
6-45
Value
Value:
Par. 6-44 to 1000000.000
Function:
Sets the analog input scaling value to correspond
to the high voltage value set in par. 6-41.
6-46
Term. X30/12 Filter Time Constant
Value:
0.001 - 10.000 s
Function:
st
A 1
order digital low pass filter time constant for
suppressing electrical noise on terminal X30/12.
Par. 6-46 cannot be changed while the motor is
running.
6-5* Analog Output 1
Parameters for configuring the scaling and limits
for analog output 1, i.e. Terminal 42. Analog out-
puts are current outputs: 0/4 – 20 mA. Common
terminal (terminal 39) is the same terminal and
has the same electrical potential for analog com-
mon and digital common connection. Resolution
on analog output is 12 bit.
6-50
Terminal 42 Output
Value:
No operation
MCO 305 0-20 mA
factory setting
How to Programme
10.0V
0.000 Unit
1500.000 Unit
0.001s
[0]
[52]
()
display text
[]
MG.33.B7.02 - VLT is a registered Danfoss trademark
MCO 305 4-20 mA
Output frequency
Reference
Feedback
Motor current
Torque rel to lim
Torque rel to rated
Power
Speed
Torque
Output freq. 4-20mA
Reference 4-20mA
Feedback 4-20mA
Motor cur. 4-20mA
Torque % lim. 4-20mA
Torque % nom 4-20mA
Power 4-20mA
Speed 4-20mA
Torque 4-20mA
Bus ctrl. 0-20 mA
Bus ctrl. 4-20 mA
Bus ctrl. 0-20 mA, timeout
Bus ctrl. 4-20 mA, timeout
Function:
Select the function of Terminal 42 as an analog
current output.
6-51
Terminal 42 Output Min Scale
Value:
0.00 – 200%
Function:
Scale the minimum output of the selected analog
signal at terminal 42, as a percentage of the max-
imum signal value. E.g. if 0 mA (or 0 Hz) is desired
at 25% of the maximum output value, then pro-
gramme 25%. Scaling values up to 100% can
never be higher than the corresponding setting in
par. 6-52.
value for use in communication via serial communication port
[53]
[100]
[101]
[102]
[103]
[104]
[105]
[106]
[107]
[108]
[130]
[131]
[132]
[133]
[134]
[135]
[136]
[137]
[138]
[139]
[140]
[141]
[142]
0%
181