Initialisation To Default Settings - Danfoss FC 300 Programming Manual

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

2. How to Programme
[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable [1] or Disable [0] via par. 0-43
LCP
.

2.1.19. Initialisation to Default Settings

2
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1.
Select par. 14-22
2.
Press [OK]
3.
Select "Initialisation"
4.
Press [OK]
5.
Cut off the mains supply and wait until the display turns off.
6.
Reconnect the mains supply - the frequency converter is now
reset.
Manual initialisation
1.
Disconnect from mains and wait until the dis-
play turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the
same time while power up for LCP 102, Graph-
ical Display
2b.
Press [Menu] while power up for LCP 101, Nu-
merical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
NB!
When you carry out manual initialisation, you also reset serial communication, RFI filter settings (par. 14-50) and fault log settings.
24
Par. 14-22 initialises all except:
14-50
8-30
8-31
8-32
8-35
8-36
8-37
15-00 to 15-05
15-20 to 15-22
15-30 to 15-32
This parameter initialises all except:
15-00
15-03
15-04
15-05
®
MG.33.M3.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide
RFI 1
Protocol
Address
Baud Rate
Minimum Response Delay
Max Response Delay
Max Inter-char Delay
Operating data
Historic log
Fault log
Operating Hours
Power-up's
Over temp's
Over volt's
Reset Keys on