Advanced commissioning
6.7 Application-specific functions
6.7.9.2

Setting the controller

Simplified representation of the technology controller
The technology controller is implemented as a PID controller (controller with proportional,
integral, and derivative action).
The inverter uses the start value when all the following conditions are simultaneously satisfied:
The technology controller supplies the main setpoint (p2251 = 0).
The ramp-function generator output of the technology controller has not yet reached the start value.
Figure 6-51
Simplified representation of the technology controller
The settings required as a minimum are marked in gray in the function diagram: Interconnect
setpoint and actual values with signals of your choice, set the ramp-function generator and
controller parameters K
You will find information on the following PID controller topics in the Internet at: FAQ
(http://support.automation.siemens.com/WW/view/en/92556266)
● Setpoint value specification: Analog value or fixed setpoint
● Setpoint channel: Scaling, ramp-function generator and filter
● Actual value channel: Filter, limiting and signal processing
● PID controller Principle of operation of the D component, inhibiting the I component and
the control sense
● Enable, limiting the controller output and fault response
254
, T
and T
.
P
I
d
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC