■ RAM data store

Command
Response

■ Software reset

Command
Response
7.9 Commands and responses (Communication/Modbus)
Slave
Function
Write start
Instruction
address
mode
address
code
information
H'06
H'00
H'00
H'04
1
1
2
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
Slave
Function
Write start
Instruction
address
mode
address
code
information
H'06
H'00
H'00
H'05
1
1
2
This writes the setting data of Operation and Adjustment levels to
internal non-volatile memory. Operation and Adjustment levels are
explained in "4.1 Setting levels and key operation" (P.4-2).
This command can be used in both setting area 0 and setting area 1.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Slave
Function
Write start
Instruction
address
mode
address
code
H'06
H'00
H'00
H'05
1
1
2
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
Slave
Function
Write start
Instruction
address
mode
address
code
H'06
H'00
H'00
H'06
1
1
2
A software reset causes the same operation as turning the power off
and on.
This command can be used in both setting area 0 and setting area 1.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
(No response)
A response is not returned to this operation command.
Related
CRC-16
2
2 bytes
Related
CRC-16
H'00
2
2 bytes
Related
information
CRC-16
H'00
2
2 bytes
Related
information
CRC-16
H'00
2
2 bytes