Omron E5AR - MANUAL 2 User Manual page 250

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Reference
Reference
Event input 1 allocation
Event input 2 allocation
Event input 3 allocation
Function
Setting
Reference
Reference
● Related setting data
"Linear current output
"Output 1 output type", "Output 3 output type" (Control initial setting
level) (P.8-42)
ev.1
Event input 4 allocation
ev.2
Event input 5 allocation
ev.3
Event input 6 allocation
• Use these settings to assign event input functions.
Setting range
Disable (0)
Write via communication OFF/ON (1)
CH1 Bank No. (Bit 0) (2)
CH1 Bank No. (Bit 1) (3)
CH1 Bank No. (Bit 2) (4)
CH1 Run/Stop (5)
CH1 Auto/Manual (6)
CH1 SP mode (Remote/Local) (7)
CH2 Bank No. (Bit 0) (8)
CH2 Bank No. (Bit 1) (9)
CH2 Bank No. (Bit 2) (10)
CH2 Run/Stop (11)
CH2 Auto/Manual (12)
CH2 SP mode (Remote/Local) (13)
Similarly,
CH3 (14 to 19)
CH4 (20 to 25)
• If the same setting is selected for different event input assignments,
the event input for which ON/OFF is determined last will be effective.
Note that when the power is turned on and the same bank No.
assignment is repeated, the event input with the higher number is
given priority.
• SP modes (Remote/Local) of CH2 to CH4 are disabled.
When the control mode is set to cascade control, assign the
following CH2 operation commands:
• CH2 Run/Stop (11)
Important
• CH2 Auto/Manual (12)
• CH2 SP mode (Remote/Local) (13) Cascade open
Cascade open / closed
● Related information
"5.7 Using event input" (P.5-29)
8.11 Control initial setting 2 level (l.2)
type" (Control initial setting level) (P.8-42)
ev.4
ev.5
ev.6
Units
l.2
Default value
0
8-47

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er

Table of Contents