Omron E5AR - MANUAL 2 User Manual page 230

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

CH
Bank
local SP (LSP)
( : 0 to 7)
Use this setting to set the SP (local SP) in each bank.
Function
Setting
Reference
Reference
CH
Bank
PID Set No.
( : 0 to 7)
Use this setting to store a PID Set No. in each bank.
Function
Setting
Reference
Reference
.lsp
• The SP of banks 0 to 7 can be set.
• When an SP is changed in "PV/SP" in Operation level, the local SP
of the currently used bank is also changed.
Setting data
Setting range
SP lower limit to
Local SP
SP upper limit
● Related information
"5.2 Control functions ■ Banks" (P.5-9)
● Related setting data
"PV/SP" (Operation level) (P.8-7)
.pid
• The PID Set No. of banks 0 to 7 can be stored.
• When the PID Set No. is set to "0", the PID set auto select function
automatically selects a PID set based on the PV or DV (deviation). If
you wish to specify a PID set, set the number of the PID set (1 to 8).
Setting data
PID Set No.
● Related information
"5.2 Control functions ■ Banks" (P.5-9)
"5.2 Control functions ■ PID sets" (P.5-12)
● Related setting data
"PID
proportional band", "PID
time" (PID setting level) (P.8-31)
"PID Automatic selection range upper limit" (PID setting level) (P.8-
32)
"PID set automatic selection data" (Expansion control setting level)
(P.8-74)
8.6 Bank setting level (l.bnk)
Units
EU
Setting range
Units
0 to 8
Integral time", "PID
l.bnk
Default value
0
l.bnk
Default value
0
derivative
8-27