Section 8 Setting data
CH
Input value 1 for input correction
Input shift 1
Input value 2 for input correction
Input shift 2
Input shift can be performed at any two points.
Function
Setting
Reference
Reference
8-20
isi.1
iss.1
isi.2
iss.2
These settings are used to set input shift 1 and input shift 2 for any two
points (input value 1 for input correction and input value 2 for input
correction) (two-point correction).
Present value (PV)
1,300
After adjustment
-200
-200
Input value 1
Setting data
Input value 1 for input
correction
Input shift 1
Input value 2 for input
correction
Input shift 2
*1 The decimal point position will vary depending on the input type.
*2 If the input type is changed, the default values of the input value for
input calibration will change to the upper and lower-limits of the
input range of the sensor type being used.
● Related setting data
"Input
type" (Input initial setting level) (P.8-36)
Adjustment value 2
Before
adjustment
Adjustment
value 1
Input
0
1,000
1,300
Input value 2
Setting range
Units
-19999 to 99999 *1
EU
-199.99 to 999.99
EU
-19999 to 99999 *1
EU
-199.99 to 999.99
EU
l.adj
Default value
-200.0
0.00
1300.0
0.00