CH
Manual output method
Manual MV initial value
This setting is used to specify how the MV is output when switching from auto mode to manual mode.
Function
Setting
Reference
Reference
8.16 Expansion control setting level (l.exc)
mant
mani
• When "Hold MV" is selected, the MV at the time of switching is held,
after which it can be changed using "Manual MV" (Operation level).
• When "Output default value" is selected, the value specified in
"Manual MV default value" is used. This can then be changed using
"Manual MV" (Operation level).
Examples of how the MV changes using the two methods are shown
below.
MV
Auto mode
Manual mode
At "MV hold"
Setting
Hold MV
Manual output method
Output initial value: init
Manual MV initial value
● Related information
"4.13 Performing manual control" (P.4-29)
● Related setting data
"Manual MV" (Operation level) (P.8-5)
MV
Time
Auto mode
Manual mode
At "Initial value output"
Setting range
Units
: hold
-5.0 to 105.0
(Standard)
%
-105.0 to 105.0
(Heating/cooling)
l.exc
Manual MV
initial value
Time
Default
value
hold
0.0
8-77