6.8 Setting areas

The E5AR/ER has two setting areas for communication: Setting area 0
and setting area 1.
In setting area 0, control continues.
As such, setting area 0 makes it possible to perform operations that
require control to be in progress, such as reading the PV, writing an
SP, and run/stop, as well as operations that do not interfere with
control. On the other hand, operations that may change control such
as writing initial setting data cannot be performed. (Note that setting
data that cannot be written can still be read.)
In setting area 1, control is stopped.
This makes it possible to perform operations such as writing initial
setting data which are not possible in setting area 0.
When the power is turned on, setting area 0 is selected. To access
setting area 1, use the "Move to setting area 1" operation command.
To return to setting area 0 from setting area 1, turn off the power or
use the "Software reset" operation command.
Power on
"Software reset" instruction
Setting area 0
Control in progress
Variable
type
C4
Communication monitor
C5
Protect level
C6
RUN level
C7
Adjustment level
C8
Adjustment level 2
C9
Bank setting level
CA
PID setting level
CB
Approximation setting level
CC
Input initial setting level
CD
Control initial setting level
CE
Control initial setting 2 level
CF
Alarm setting level
D0
Display adjustment level
D1
Communications setting level
D2
Special function setting level
D3
Expansion control setting level

6.8 Setting areas

Setting area 1
"Move to setting
area 1" instruction
Control stop
Description
Area
Setting area 0
(During control)
Setting area 1
(Control stop)
6-13