Section 3 Typical Control Examples
Adjustment level (ch 2)
Present value ( PV ) / SP/
2
bank
MV
0
l.adj
RSP
Ch 2
2
spmd
SP mode
rsp
lsp
D
l.adj
RSP
RUN level (Ch 2)
Present value ( PV ) / SP /
2
230.0
MV
0.0
230.0
U
50.0
RSP
Adjustment level
Present value ( PV ) / SP /
2
bank
MV
0
l.adj
RSP
Ch 2
2
at
AT Execute/Cancel
off
0
U
l.adj
RSP
Ch 2
2
spmd
SP mode
lsp
rsp
U
l.adj
RSP
3-16
3. Press the L key less than 1 second to move from "RUN level" to
"Adjustment level".
4. Press the M key repeatedly to select the secondary (ch 2) "spmd: SP
mode". Press the D key to set the SP mode to "lsp: Local SP".
The RPS operation indicator is off in local SP mode, indicating independent
control (cascade open) in the secondary loop.
5. Press the L key repeatedly to return to "RUN level". The secondary (ch 2)
"PV/SP/MV" will appear. Set the secondary SP to "230.0", which is the PV
obtained in step 2.
6. Press the L key less than 1 second to move from "RUN level" to
"Adjustment level".
7. Press the M key to select the secondary (ch 2) "at: AT Execute / Cancel".
Press the U to change the set value to "0" and run AT. During AT the
automatically selected PID Set No. is displayed and display 1 (at) blinks.
Display 2 shows "off" when AT finishes, and display 1 (at) stops blinking.
8. Press the M key to select the secondary (ch 2) "spmd: SP mode". Press
the U key to select "rsp: Remote SP".
The RSP operation indicator will light up in remote SP mode to indicate
cascade control (cascade closed).