● SP mode
• This function is only effective when the control mode is control with
remote SP.
• When the event input is ON, the remote SP (RSP) is used as the SP
and the "RSP" operation indicator lights up. When the event input is
OFF, the local SP (LSP) is used as the SP. The content of the event
input is reflected in "SP mode" (Adjustment level).
• This setting data is an operation command that is particular to a
single channel.
• Operation is as follows based on the event input ON/OFF state.
Event input
OFF
ON
Setting data
Symbol
name
Event input 1 to 6
ev.
assignment
: 1 to 6
5.7 Using event input
Description
Local SP mode
Remote SP mode
Level
Use
(Display 3)
Control initial
Specify event
setting 2 (l.2)
input
5-31