Omron E5AR - MANUAL 2 User Manual page 260

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

CH
Standby sequence restart
Function
Setting
Reference
Reference
rest
Alarm types 1 to 4 = With standby sequence
• Use this setting to select the condition for restarting the standby
sequence after it has been canceled.
• Condition A: Operation startup (including power on), when an alarm
value (alarm upper- and lower-limit) or input shift value
(input value for input calibration 1 and 2, input shift 1
and 2) is changed, or when the SP is changed.
• Condition B: Power on
• The following example shows operation using a lower-limit alarm
with standby sequence.
Alarm point
(after change)
Alarm point
Alarm output: Condition A
Alarm output: Condition B
• After changing the standby sequence restart setting, a software
reset must be executed or the power turned off and on to make the
change take effect.
Setting range
a: Condition A
b: Condition B
● Related setting data
"Alarm
type" (Alarm setting level) (P.8-54)
"Alarm
latch" (Alarm setting level) (P.8-55)
8.12 Alarm setting level (l.3)
Condition A only
SP change
O : Standby sequence
Condition A only
O : Standby sequence
Units
Default value
a: Condition A
l.3
Alarm hysteresis
off point
restart point
8-57