■ Write setting data to protect level

Command
Response

■ Write setting data (Communication/Modbus)

Command
7.9 Commands and responses (Communication/Modbus)
Slave
Function
Write start
Number of
Address
mode
address
elements
H'10
H'0002
1
1
2
Address
H'0500
Operation adjustment protect
H'0502
Initial setting level protect
H'0504
Setting change protect
H'0506
PF key protect
This command writes setting data to Protect level. Protect level is
explained in "4.1 Setting levels and key operation" (P.4-2).
This command is used in setting area 0. If used in setting area 1, an
error will result.
To use this command, use the "Write via communication" operation
command to enable "Write via communication", and then use the
"Move to protect level" operation command to move to "Protect level".
Slave
Function
Write start
Number of
address
mode
address
elements
H'10
1
1
2
The above indicates a normal end. For information on error responses,
see "7.6 Writing to the variable area" (P.7-12).
Slave
Function
Write start
Number of
address
mode
address
elements
H'10
1
1
2
Byte
count
Write data
H'04
2
1
4 bytes
Setting data
CRC-16
2
2
Byte
Write data
count
Data 1
Data 1
Most significant Least significant
2
1
Number of elements 2 bytes
Data n
Data n
Most significant Least significant
CRC-16
2
CRC-16
2
7-19