■ Wiring

■ Settings

IN1 is connected to the adjustment system and IN2 is connected to the
sensor in the reference system. (A flow meter is connected to IN1, a
sand weight scale is connected to IN2, and a pump (drive inverter) is
connected to OUT1.)
When using the E5AR-QQ43W-FLK, wire as shown below.
Sand
Sensor 2 flow meter
Sand weight meter
Sensor 2
The scale of sensor 1, which measures the flow of dye, is 0.0 to 25.0
kg/s, and the scale of sensor 2, which measures the weight of sand, is
0.0 to 500.0 kg/s. The ratio value is set to 0.05 so that the proportion of
sand to dye will be 110 : 5.
Related setting data and settings are as follows:
Input 1 type switch
Input 2 type switch
Input 1 type
Ch 1 scaling input value 1
Ch 1 scaling display value 1
Ch 1 scaling input value 2
Ch 1 scaling display value 2
Ch 1 decimal point position
Input 2 input type
Output type of output 1
Output type of linear current output 1
Control mode
Straight-line approximation 1
Straight-line approximation 2
Straight-line approximation 1, Straight-line approximation 2
See the setting examples on the next page
Analog parameter 1
SP mode
3.5 Ratio control of dyeing machines
A
B
1
100 - 240 V AC
2
Color liquid
3
4
5
6
1
2
3
P
4
4 - 20 mA
5
OUT1
6
F
G
H
= ANALOG
= ANALOG
= 15: 4 to 20 mA
= 4
= 0
= 20
= 250
= 1
= 15: 4 to 20 mA
= 1: Current output (initial setting)
= 1: 4 to 20 mA (initial setting)
= 4: Ratio control
= on: Enable
= on: Enable
= 0.05
= rsp: Remote SP
C
D
E
1
2
3
4
5
6
1
IN2
2
3
4
IN1
5
6
I
J
K
3-19