Operation procedure
Display PID* selection
1
d.pid
1
U
l.pid
P (proportional band)
1
3.p
10.00
U
l.pid
● PID set automatic
selection
Automatic selection
PID* set
range upper limit
1
200.0
PV (present
2
400.0
value(PV)) 24.00
3
500.0
4
600.0
5
700.0
6
800.0
7
1000.0
8
1300.0
Internal fixed
value: 999.9% FS
Set "P" (proportional band) of PID set 3 to 50.00 %FS.
1. Press the L key repeatedly to move to "PID setting level" (Display 3 shows
l.pid).
2. Use the UD keys to set "Display PID selection" to "3".
3
3. Press the M key to select "P (Proportional band)". To check the bank
number, view the leading digit of the setting data.
4. Use the UD keys to set the value to "50.00".
50.00
• A PID Set No. (1 to 8) is set in "PID Set No." in "Bank setting level".
For this reason, PID control parameters different from the selected
bank can be used during operation.
• If "PID Set No." is set to "0", the PID set is automatically selected
(PID auto selection) according to previously set conditions.
When "PID Set No." is set to "0" in a bank, the PID set is automatically
selected according to previously set conditions.
In the example at left ("PID set selection data" is set to "PV"),
When PV
200.0°C, PID Set 1 is used
When 200.0 < PV
"PID automatic selection range upper limit" is set so that the value
increases as the PID Set No. increases.
However, note that the value for PID Set 8 is internally fixed at
"Automatic selection range upper limit" = 999.9% FS.
To prevent chattering when changing PID sets, hysteresis can be set
in "PID set selection hysteresis".
PV or DV (deviation) can be selected for the "PID set selection data".
Setting data
Banks 0 to 7 PID Set No.
PID Sets 1 to 8 Automatic
selection range upper limit
PID set selection data
PID set selection hystere-
sis
5.2 Control functions
400.0°C, PID Set 2 is used
Setting range
0: Auto selection
1 to 8: PID Sets 1 to 8
-19999 to 99999
0: PV, 1: DV
0.10 to 99.99
Default
Units
value
0
EU
1450.0
0: PV
%FS
0.50
5-13