Section 4 Settings Required for Basic Control
4-6
1, Power on
RUN level
Control stops
Control stops
Input initial setting level
Input type is
displayed
Input initial setting level
Change the input
2, Input specification
type with the UD
setting
key
Control initial setting level
Check "Output 1:
Output type".
3, Control mode setting
Check the control
mode
Alarm setting level
Check the alarm
type
4, Alarm type setting
Change the alarm
type with the UD
key
Power on
25. 0
Present value (PV) /
0
0
.
0
SP / MV
. 0
Hold down for at least 3 seconds.
l.0
Display 3 will show
(input initial setting level).
i1-t
Input 1 type
2
2: K(1) - 200.0 to 1300.0 C
l. 0
UD
i1-t
Input 1 type
0
2 0: Pt100(1)-200.0 to 850.0 C
l.0
Press less than 1 second.
Display 3 will show l. 1 (control initial setting level).
o1-t
Output 1 type
0
0: Pulse voltage output
l. 1
M
mode
Control mode
0
0: Standard control
l.1
Press twice less than 1 second.
Display 3 will show l.3 (alarm setting level).
alt1
Alarm 1 type
2
2: Upper-limit alarm
l.3
M
alt2
Alarm 2 type
8
2 8: Absolute-value upper-limit alarm
l. 3
Press for at least 1 second to return to RUN level.
l.0
l. 0
1. Refer to input type list
(page 8-36)
l.1
2. Refer to output type list
(page 8-42)
indicates that the key is
pressed several times to
switch to desired setting
data.
l.3
3. Refer to alarm type list
(page 8-54)