Controller Status Read (Communication/Compoway/F) - Omron E5AR - MANUAL 2 User Manual

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Section 6 Communication (CompoWay/F)

■ Controller status read (Communication/CompoWay/F)

Command
Response
◆ Operation state
◆ Related information
6-30
MRC
SRC
"06"
"01"
This command reads the operation status of the E5AR/ER.
The command can be used in any state of the E5AR/ER.
MRC
SRC
Response code
"06"
"01"
"0000"
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
7
6
5
4
3
2
1
0
Bit position
0
0
0
0
ch4
ch3
ch2
ch1
Bit position
Operation state
00
01
(MV at PV error output)
10
(Including setting area 1)
11
The operation state of each channel is indicated using a 2-bit code.
7
6
5
4
3
2
1
0 Bit position
Bit position
Status
0
Blank
1
Blank
2
CT input error
3
RSP input error
4
Potentiometer error
5
Exceeds display range
6
Input error
7
Blank
* OR of channels set in "Number of enabled channels".
* When the channel does not exist, is "Not occurred: 0".
* If this command is used in setting area 1, the related information is
undefined.
Operation
state
Related information
Operating
Error
Stopped
Manual mode
Bit description
0
Not occurred
Not occurred
Not occurred
Not occurred
Not occurred
1
Occurred
Occurred
Occurred
Occurred
Occurred

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er

Table of Contents