Section 8 Setting data
CH
Hysteresis (heating)
Hysteresis (cooling)
This sets the Hysteresis to enable stable operation when control is switched ON/OFF.
Function
Setting
Reference
Reference
CH
Control period (heating)
Control period (cooling)
Function
Setting
Reference
Reference
8-16
hys
chys
• For standard control, "Hysteresis (heating)" is used. "Hysteresis
(cooling)" cannot be used.
• For heating/cooling control, the Hysteresis can be set separately for
heating and cooling. Use "Hysteresis (heating)" for heating and
"Hysteresis (cooling)" for cooling.
• This setting appears when Proportional band = 0.00
Setting range
0.01 to 99.99
● Related setting data
"PID Proportional band (PID setting level) (P.8-31)
cp
c-cp
• This sets the output period. When setting this value, take controlla-
bility and product life (if the connected manipulation device is a
relay) into consideration.
• "Control period (heating)" is used for standard control.
• For heating/cooling control, control periods can be set separately for
heating and cooling.
Setting data
Control period
(heat)
Control period
(cooling)
● Related setting data
"PID Proportional band (PID setting level) (P.8-31)
ON/OFF Control (P = 0.0)
Units
%FS
Setting range
Units
0.2 to 99.0
Sec
0.2 to 99.0
Sec
l.adj
Default value
0.10
l.adj
Default value
20.0
20.0