Setting
CH
PF1 monitor/setting item 1 to
PF1 monitor/setting item 5
PF2 monitor/setting item 1 to
PF2 monitor/setting item 5
Function
Setting
Reference
Reference
8.15 Advanced function setting level (l.adf)
Setting data
Setting range
off : Disable
run : Run
stop: Stop
PF1 setting
r-s : Run/Stop toggle
allr: Run all
alls: Stop all
at
: AT Execute/Cancel
toggle
PF2 setting
bank: Bank scroll
a-m : A key
pfdp: Monitor/setting item
pf1.1 to
pf1.5
pf2.1 to
pf2.5
• When one or both PF keys are set to monitor/setting item, "Monitor/
setting item 1" through "Monitor/setting item 5" of each key must be
set to the desired values among 0 to 19 below.
• Each time a PF key is pressed, the display scrolls to the next
monitor/setting item in order from "Monitor/setting item 1" to "Monitor
setting item 5".
Setting
PF1 Monitor/
0: Disable
setting item 1
1: PV/SP/Bank
Configurable (SP)
PF1 Monitor/
2: V/SP/MV
setting item 2
Configurable (SP)
PF1 Monitor/
3: PV/DV Monitor only
setting item 3
4: Proportional band (P) Configurable
PF1 Monitor/
5: Integral time (I) Configurable
setting item 4
6: Derivative time (D) Configurable
PF1 Monitor/
7: Alarm 1 Configurable
setting item 5
8: Alarm upper limit 1 Configurable
9: Alarm lower limit 1 Configurable
PF2 Monitor/
10: Alarm 2 Configurable
setting item 1
11: Alarm upper limit 2 Configurable
PF2 Monitor/
12: Alarm lower limit 2 Configurable
setting item 2
13: Alarm 3 Configurable
PF2 Monitor/
14: Alarm upper limit 3 Configurable
setting item 3
15: Alarm lower limit 3 Configurable
PF2 Monitor/
16: Alarm 4 Configurable
setting item 4
17: Alarm upper limit 4 Configurable
18: Alarm lower limit 4 Configurable
PF2 Monitor/
19: Bank No. Configurable
setting item 5
● Related setting data
"PF1 setting", "PF2 setting" (Advanced function setting level) (P.8-68)
Units
a-m: A key
r-s: Run/
Stop toggle
PF key set to monitor/setting item
Setting range
Default value
l.adf
Default
Units
value
1
0
0
0
0
1
0
0
0
0
8-69