Section 8 Setting data
Reference
Reference
CH
Motor calibration
Function
Operation
Reference
Reference
CH
Travel time
Function
Setting
Reference
Reference
8-52
● Related setting data
"Broken-line approximation 1 Input 1" to "Broken-line approximation
1 Input 20", "Broken-line approximation 1 Output 1" to "Broken-line
approximation 1 Output 20" (Approximation setting level) (P.8-34)
calb
• Use this setting to run motor calibration. If you are going to monitor
the valve opening, be sure to execute this setting. (During execution
the display cannot be changed.)
• Executing this setting also resets "Travel time".
• When this setting is accessed, the set value is "off".
• Select "on" to run motor calibration.
• When motor calibration ends, the setting automatically reverts to
"off".
● Related information
"3.3 Position proportional control of a ceramic kiln ■ Settings for
position proportional control" (P.3-12)
● Related parameters
"Travel time" (Control initial setting 2 level) (P.8-52)
mot
• Set the time from valve completely open to valve completely closed.
• This parameter is automatically set when "Motor calibration" is run.
Setting range
1 to 999
● Related information
"3.3 Position proportional control of a ceramic kiln ■ Settings for
position proportional control" (P.3-12)
● Related parameters
"Motor calibration" (Control initial setting 2 level) (P.8-52)
Position proportional type
Position proportional type
Units
Default value
Sec
30
l.2
l.2