CH
Bumpless at RUN
Function
Setting
CH
Operation at potentiometer input error
Function
Setting
Reference
Reference
8.16 Expansion control setting level (l.exc)
● Related information
"4.10 Determining the PID constants (AT, manual settings)" (P.4-20)
● Related setting data
"AT Execute/Cancel" (Adjustment level) (P.8-13)
rbmp
• When "Bumpless at RUN" is enabled, an integral MV correction
(bumpless) is performed to prevent abrupt changes in the MV when
switching from stop to run.
• Even when the setting is disabled, the bumpless correction is
performed when PID values change (including changing the PID set)
and when AT ends or is stopped.
Setting range
off : Disable
on : Enable
pmec
• This setting is used to select whether control is stopped or changed
to floating control when a potentiometer error occurs during closed
control in position proportional control.
Setting range
off : Stop
on : Continue
● Related setting data
"Closed/Floating" (Control initial setting level) (P.8-44)
Units
Default value
off: Disable
Position proportional type
Units
Default value
off: Stop
l.exc
l.exc
Closed control
8-79