Setting Data For User Calibration - Omron E5AR - MANUAL 2 User Manual

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Section 9 User calibration

9.1 Setting data for user calibration

• To perform user calibration, enter "1201" in "Move to user calibration" in Special setting level. The
controller will enter calibration mode and "adj" will appear in the display.
• If the "Move to user calibration" setting does not appear, set "Initial setting protect" to "0" in Protect level
and then move to Special setting level.
• Calibration is ended by turning off the power.
• The setting data for input calibration is shown below.
(The last digit of Display 1 shows the input number. The example below shows "1" for input 1. In the
case of input 2, the display would show "p390.2".)
adj
(Aging timer)
Input type 1
PT100 (1) <0>
PT100 (2) <1>
p390.1
p160.1
p 20.1
p 40.1
str.i1
1: < > shows set value (in general) of input type.
9-2
K (1)<2>, J (1)<4>
K (2)<3>, J (2)<5>
E (1)<7>, L (1)<8>
T (2)<6>, U (2)<9>
N (1)<10>, W (1)<14>
R (2)<11>, S (2)<12>
B (2)<13>
1t53.1
2t22.1
1t-6.1
2t-6.1
bia5.1
bia5.1
◆ Output calibration setting data
The setting data for output calibration is shown below. The display
varies depending on the output type of each output.
(In the following example, the last digit of Display 1 shows "1" for
output 1. For output 2, this would be "oa20.2".)
str.i1
At linear current output
oa20.1
oa 4.1
str.o1
4 to 20 mA <15>
1 to 5 V <17>
0 to 20 mA <16>
0 to 5 V <18>
a 20.1
1V 5.1
a
1.1
1V 1.1
(Store input calibration value)
0 to 10 V <19>
2V10.1
2V 1.1