Section 7 Communication (Modbus)
■ Move to setting area 1
Command
Response
■ Move to protect level
Command
Response
7-26
Slave
Function
Write start
Instruction
address
mode
address
code
H'06
H'00
H'00
H'07
1
1
2
Use this command to move to setting area 1.
The command is used in setting area 0. Nothing happens if the
command is used in setting area 1.
If the command is used when "Initial setting level protect" is set to "2
(Disable move to input initial setting level)", an operation error will
result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Slave
Function
Write start
Instruction
address
mode
address
code
information
H'06
H'00
H'00
H'07
1
1
2
2
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
Slave
Function
Write start
Instruction
address
mode
address
code
information
H'06
H'00
H'00
H'08
1
1
2
2
Use this command to move to protect level. Protect level is explained
in "4.1 Setting levels and key operation" (P.4-2).
This command is used in setting area 0. If used in setting area 1, an
operation error will result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Slave
Function
Write start
Instruction
address
mode
address
code
H'06
H'00
H'00
H'08
1
1
2
2
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
Related
CRC-16
information
H'00
2
2 bytes
Related
CRC-16
H'00
2 bytes
Related
CRC-16
H'00
2 bytes
Related
information
CRC-16
H'00
2 bytes