CH
SP upper limit
SP lower limit
Function
Setting
Reference
Reference
Control mode
Use this setting to select the control mode.
Function
sl-h
sl-l
• Use this setting to set upper and limits for the SP setting. The SP
can only be set between these limits. Note that if the limits are
changed and a previously set SP falls outside of the limits due to the
change, the SP will automatically change to the upper or lower limit.
• If the input type and temperature units are changed, the settings will
change to the upper and lower limits of the sensor.
• The decimal point position depends on the selected sensor. In the
case of analog input, the decimal point position is determined by the
"Decimal point position" setting.
Setting data
Setting range
Temperature: SP lower
limit + 1 to upper limit of
input range
SP upper limit
Analog: SP lower limit + 1
to smaller of "99999" and
"display value equivalent
of input upper limit"
Temperature: Lower limit
of input range to SP
upper limit 1
SP lower limit
Analog: Larger of "-
19999" and "display value
equivalent of input lower
limit" to SP upper limit - 1
● Related setting data
"Input
type" (Input initial setting level) (P.8-36)
"Input
temperature units" (Input initial setting level) (P.8-37)
mode
• On single-input or 4-input types, select standard control or heating/
cooling control.
• On two-input types, select standard control, heating/cooling control,
standard control with remote SP, heating/cooling control with remote
SP, proportional control, cascade standard control, or cascade
heating/cooling control.
8.10 Control initial setting level (l.1)
Units
EU
EU
l.1
Default value
1300.0
-200.0
l.1
8-43