Section 8 Setting data
Sensor induction noise reduction
This function reduces induction noise from the power source in the input.
Function
Setting
Reference
Reference
Move to advanced function setting level
This function is used to move to Advanced function setting level.
Function
Setting
Reference
Reference
8-40
snc
• This reduces induction noise in the input according to the frequency
of the power source.
• Select 50 Hz or 60 Hz as appropriate for the power source used for
the controller.
Setting range
50hz: 50 Hz
60hz: 60 Hz
● Related data
"Input
type" (Input initial setting level) (P.8-36)
amov
• Enter a password to move to Advanced function setting level.
• The password is set to "-169". After entering "-169", press the M
key or wait two seconds and you will move to Advanced function
setting level.
Setting range
-1999 to 9999
● Related setting data
"Initial setting protect (Protect level) (P.8-3)
Units
Default value
50hz: 50 Hz
"Initial setting protect" is set to "0"
Units
Default value
0
l.0
l.0