Section 8 Setting data

8.7 PID setting level (

This level contains the PID value, MV limit, and alarm settings for each PID set. To move to a PID set, use
the "Display PID set select" setting at the beginning of PID setting level.
Power on
Adjustment
Operation level
level
l. adj
L key less
than 1 second
L key less
than 1 sec
Approximation
PID setting
setting
level
level
l. tec
l. pid
L key less
than 1 second
CH
Display PID selection
Use this setting to select the PID set that you wish to display.
Function
Setting
Reference
Reference
8-30
l.pid
Adjustment 2
level
l. ad2
L key less
than 1 second
L key less
than 1 second
Bank setting
level
l. bnk
L key less
than 1 second
Control in
progress
d.pid
• Set the number of the PID set that you wish to display.
• Up to 8 PID sets (PID Set Nos. 1 to 8) can be used. PID values, MV
upper and lower limits, and automatic selection range upper limit are
stored in each PID set.
Setting data
Display PID
selection
* Selected PID set
● Related setting data
"Bank No." (Adjustment level) (P.8-13)
)
PID setting level
l.pid
CH
d.pid
Display PID selection
PID1
1
PID2
2
PID3
3
U
M
CH
1.p
10.00
CH
M
CH
1.i
233.0
CH
M
CH
1.d
CH
40.0
M
CH
1.ol-h
CH
100.0
8.ol-h
M
CH
1.ol-l
CH
0.0
8.ol-l
M
CH
1.
aut
CH
8.
1450.0
1450.0
M
1 Position proportional type: 0.01 - 999.99
2 Position proportional (floating control) type: 0.1 - 3999.9
3 Analog type: -10% to 110% of scaling display range, with
a maximum of -19999 to 99999
Setting range
1 to 8
D
8
PID8
M
8.p
8.P: PID8 Proportional band
0.00 - 999.99 (standard) 1
10.00
M
8.I: PID8 Integral time
8.i
0.0 - 3999.99 (standard,
233.0
position proportional
M
(closed control)) 2
8.d
8.D:PID8 Derivative time
40.0
0.0 - 3999.9
M
8.OL-H:PID8 MV upper limit
MV lower limit
100.0
0.1 - 105.0
M
8.OL-L:PID8
MV lower limit
0.0
-5.0 - MV upper limit - 0.1
M
8.AUT:PID8
Automatic selection range
aut
upper limit
-10% to 110% (temperature)
M
of sensor setting range 3
l.pid
Units
Default value
*