Section 8 Setting data
Auxiliary output 1 allocation
Auxiliary output 2 allocation
Function
Setting
Reference
Reference
8-48
sbo.1
Auxiliary output 3 allocation
sbo.2
Auxiliary output 4 allocation
• Use these settings to assign output content to auxiliary outputs.
Setting range
Disable (0)
CH1 Alarm 1 (1)
CH1 Alarm 2 (2)
CH1 Alarm 3 (3)
CH1 Alarm 4 (4)
CH1 Input error (5)
CH1RSP Input error (6)
Disabled (7)
*
U-ALM (8)
Alarm 1 OR output of all channels (9)
Alarm 2 OR output of all channels (10)
Alarm 3 OR output of all channels (11)
Alarm 4 OR output of all channels (12)
Input error OR output of all channels (13)
RSP Input error OR output of all channels (14)
Disable (15)
CH2 Alarm 1 (16)
CH2 Alarm 2 (17)
CH2 Alarm 3 (18)
CH2 Alarm 4 (19)
CH2 Input error (20)
CH2RSP Input error (21)
Disable (22)
Similarly,
CH3 (23 to 29)
CH4 (30 to 36)
* On a multi-point input type, assignment data can be set for channels
2 and higher as appropriate for the number of channels. U-ALM
output will be OR output of alarm functions 1 to 4 of all channels.
● Related information
"4.11 Using auxiliary output" (P.4-23)
l.2
sbo.3
sbo.4
Units
Default value
1 to 4