Reference
Reference
CH
PV decimal point display
This setting can be used to not show the digits of the PV after the decimal point.
Function
Setting
Reference
Reference
Setting data
Setting range
Temperature:
Lower limit of sensor set-
ting range to upper limit of
sensor setting range
Analog:
Remote SP
Larger of -19999 and "dis-
lower limit
play value equivalent to
input lower limit" to smaller
of 99999 and "display
value equivalent to upper
input limit"
● Related setting data
"Input
type" (Input initial setting level) (P.8-36)
"Input
temperature units" (Input initial setting level) (P.8-37)
"Control mode" (Control initial setting level) (P.8-43)
"SP upper limit", "SP lower limit" (Control initial setting level) (P.8-43)
Note: When the input type of remote SP input is set to temperature
input, be sure to set the input type of the main input to the same
setting as the input type of remote SP input.
If the input type of remote SP input is set to temperature input
and the upper and lower limits of remote SP are not the same
as the upper and lower limits of the sensor setting range of the
input type of remote SP input, it will not be possible to obtain a
correct remote SP value.
pvdp
• When "PV decimal point display" is turned OFF, the digits of the PV
after the decimal point are not shown. When turned ON, the digits
after the decimal point are shown according to the input type setting.
Setting range
off : OFF
on : ON
● Related data
"Input
type" (Input initial setting level) (P.8-36)
8.9 Input initial setting level (l.0)
Units
EU
-200.0
Temperature input
Units
Default value
on: ON
Default value
l.0
8-39