Section 6 Communication (CompoWay/F)
■ Monitor value / setting data compound read
(Communication/CompoWay/F)
Command
Response
6-16
Variable
MRC
SRC
type
Address
"01"
"04"
Variable
Address
type
"0000"
"0100"
"C4"
"0200"
"0300"
"0000" to "007F"
"0100" to "017F"
"C5" to "CB"
"0200" to "027F"
"0300" to "037F"
"0000" to "0039"
"0100" to "0139"
"CC" to "D3"
"0200" to "0239"
"0300" to "0339"
Multiple monitor values or setting data can be read by sending a single
command. Up to 20 items can be read even if the addresses are not
contiguous.
To specify the variable type or address, see "Appendix Setting list"
(P.A-6). The upper limit of an address will vary depending on the
variable type.
This command can be used in both setting area 0 and setting area 1.
If an area type error or a setting data error occurs in any of the data
being read, no data will be read.
MRC
SRC
Response code Variable type
"01"
"04"
"0000"
Response codes: The above indicates a normal end. For the response
codes, see "6.5 Reading the variable area" (P.6-9).
Variable
Address
Bit position
type
"00"
Variable type
Address
Setting data
Ch
Explanation
1
2
Monitor values
3
4
1
2
Setting data of setting area 0
3
4
1
2
Setting data of setting area 1
3
4
Data
Type
Monitor value / Setting data
Variable type
Type
Monitor value / Setting data
Bit position
"00"
Bit position
"00"
Data