Set value
Input type
15
4 to 20 mA
16
0 to 20 mA
17
1 to 5 V
18
0 to 5 V
19
0 to 10 V
Set the input type switch according to the "Input type" setting.
The initial settings are "2" and "TC.PT".
■ Scaling
25.0
0.0
0.0
i1-t
15
l.0
inp.1
5
l.0
dsp.1
0
l.0
inp.2
20
l.0
dsp.2
1000
l.0
Setting range
(°C)
One of the following ranges is displayed depending
on the scaling
-19999 to 99999
-1999.9 to 9999.9
-199.99 to 999.99
-19.999 to 99.999
-1.9999 to 9.9999
When analog input (voltage input, current input) is used,
Hint
scaling according to the type of control is possible.
Setting the display to show 0.0 for an input value of 5 mA and 100.0 for
20 mA when the input 1 type is set to "4 to 20 mA".
1. Hold the L key down for at least 3 seconds to move from "RUN level" to
"Input initial setting level".
2. Make sure that "i1-t: Input 1 input type" is "15: 4 to 20 mA".
3. Press the M key repeatedly to select "inp.1: Scaling input value 1".
Set to "5" with the UD keys.
4. Press the M key to select "dsp.1: Scaling display value 1".
Set to "0" with the UD keys.
5. Press the M key to select "inp.2: Scaling input value 2".
Set to "20" with the UD keys.
6. Press the M key to select "dsp.2: Scaling display value 2".
Set to "1000" with the UD keys.
4.4 Setting the input type
Input type
switch
(°F)
ANALOG
TC.PT
IN1
TYPE
ANALOG
4-9