Section 9 User calibration
adj
30
l.cal
Input types 2, 4, 7, 8, 10, 14
1t53.1
d72b3
l.cal
Input types 3, 5, 6, 9, 11, 12, 13
2t22.1
c8496
l.cal
Input types 2, 4, 7, 8, 10, 14
1t-6.1
76196
l.cal
9-6
Follow these steps to perform calibration when thermocouple input is
selected.
1. Connect the power supply.
2. Connect the DC reference current/voltage generator (STV in the following),
precision digital meter (DMM in the following), and cold junction compen-
sator (a ZERO-CON is used as an example in the following) to the input
terminals of the thermocouple as shown below.
STV
DMM
Leave open
ZERO-CON
OUTPUT
INPUT
3. Turn on the power.
4. Move to calibration level.
A 30-minute aging time begins. Perform aging using this time as a
guideline. When 30 minutes elapses, Display 2 will show "0".
Note that you can proceed to the next stop before the display shows "0".
5. Press the key M to obtain the display at left.
The count value that was input will appear in Display 2 in hexadecimal. Set
the STV as follows:
• For input types 2, 4, 7, 8, 10, and 14: 53 mV
• For input types 3, 5, 6, 11,12, and 13: 22 mV
Wait until the count in Display 2 is sufficiently stable and then press the D
key. This tentatively saves the calibration data at this point.
6. Press the key M to obtain the display at left.
Set the STV to -6 mV.
Wait until the count in Display 2 is sufficiently stable and then press the D
key. This tentatively saves the calibration data at this point.
_
+
Compensating wire of selected thermocouple
However, for thermocouples E, R, S, W, and B,
compensating wire of thermocouple K is used.