■Setting method
Configure the double input discrepancy detection setting in "Double input discrepancy detection setting" and "Double input
discrepancy detection type" from the "Parameter Processing of Device Station" window of the engineering tool.
For the procedure to display the "Parameter Processing of Device Station" window, refer to the following.
Page 72 Parameter Settings
Item
Double input discrepancy detection setting Xn, Xn+1
*1 n: Even number
• When an item other than "1: Double wiring (NC/NC)" is selected in "Wiring selection of input", only "1: Do
not detect" can be selected for "Double input discrepancy detection setting".
• When double input discrepancy errors do not need to be detected during equipment maintenance including
system start-up and inspection, select "1: Do not detect".
Item
Double input discrepancy detection type Xn, Xn+1
*2 n: Even number
When "1: Do not detect" is selected in "Double input discrepancy detection setting", the setting of "Double
input discrepancy detection type" is ignored.
Double input discrepancy detection time
When the double input discrepancy detection time is set, an error does not occur during the set detection time even if double
input discrepancy is detected. The following table lists the relation of each double input evaluation result and the double input
discrepancy detection time.
Input terminal state
Time passed after the discrepancy
state is applied
*1
*1
Xn
Xn+1
OFF
OFF
OFF
ON
< Double input discrepancy detection time
 Double input discrepancy detection time
OFF
ON
ON
OFF
< Double input discrepancy detection time
 Double input discrepancy detection time
ON
OFF
ON
ON
*1 n: Even number from 0 to 1E for the NZ2GFSS2-32D-S1 or from 0 to 6 for the NZ2GFSS2-8D-S1 and the NZ2GFSS2-16DTE-S1
*2 m: Safety device address (even number from 0 to 1E for the NZ2GFSS2-32D-S1 or from 0 to 6 for the NZ2GFSS2-8D-S1 and the
NZ2GFSS2-16DTE-S1) assigned to the master station
Setting range
*1
0: Detect
1: Do not detect
Setting range
*2
0: Discrepancy detection time specified
1: Discrepancy detection time not specified
Safety remote input
*2
SA\Xm
OFF
OFF
OFF
OFF
OFF
ON
Evaluation result of double
inputs
*2
SA\Xm+1
OFF
OFF (Normal)
OFF
OFF (Discrepancy)
OFF
Double input discrepancy detection
error
OFF
OFF (Discrepancy)
OFF
Double input discrepancy detection
error
ON
ON (Normal)