Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 75

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Parameter list
■NZ2GFSS2-32D-S1
Item
Station parameter
Transmission interval monitoring time
Operation setting of external power supply voltage error detection
Basic module
Wiring selection of input
parameter
Input response time
Double input discrepancy
detection setting
Double input discrepancy
detection type
Double input discrepancy auto recovery setting
Double input discrepancy
detection time
Input dark test execution
setting
Input dark test pulse OFF time
Number of pulse output for input dark test
Ext. module
Ext. module 1_Wiring
1_Extension
selection of output
module
*1
parameter
Ext. module 1_Output dark
test execution setting
Ext. module 1_Output dark
test pulse OFF time
Ext. module 1_Number of pulse output for output dark test
*1 This parameter can be set only when a safety extension module is connected.
Set all the items of the parameters displayed. If any item is left blank, the parameters cannot be written to the
safety remote I/O module.
Wiring selection of input X0 to Wiring
selection of input X1F
Input response time X0 to Input
response time X1F
Double input discrepancy detection
setting X0_X1 to Double input
discrepancy detection setting
X1E_X1F
Double input discrepancy detection
type X0_X1 to Double input
discrepancy detection type
X1E_X1F
Double input discrepancy detection
time X0_X1 to Double input
discrepancy detection time
X1E_X1F
Input dark test execution setting X0
to Input dark test execution setting
X1F
Ext. module 1_Wiring selection of
output Y0 to Ext. module 1_Wiring
selection of output Y7
Ext. module 1_Output dark test
execution setting Y0 to Ext. module
1_Output dark test execution setting
Y7
Ext. module 1_Output dark test
pulse OFF time Y0 to Ext. module
1_Output dark test pulse OFF time
Y7
Setting range
Reference
4 to 1000ms (default: 35)
Page 37 Safety remote I/O
module safety response time
0: Stop safety communication
Page 110 Operation Setting
(default)
Function at Detection of
1: Continue safety
External Power Supply
communication (Without output
Voltage Error
interlock)
2: Continue safety
communication (With output
interlock)
0: Not used (default)
Page 85 Safety input wiring
1: Double wiring (NC/NC)
selection function
2: Single wiring
0: 1ms (default)
Page 88 Safety input
1: 5ms
response time setting
2: 10ms
function
3: 20ms
4: 50ms
0: Detect (default)
Page 93 Double input
1: Do not detect
discrepancy detection
function
0: Discrepancy detection time
specified (default)
1: Discrepancy detection time not
specified
0: Not used (default)
1: Used
1 to 6000 (default: 1)  10ms
0: Perform (default)
Page 101 Input dark test
1: Do not perform
function
0: 400s (default)
1: 1ms
2: 2ms
0: 1 time (default)
1: 2 times
2: 3 times
0: Not used (default)
Page 89 Safety output wiring
1: Double wiring (Source/Source)
selection function
2: Single wiring
0: Perform (default)
Page 105 Output dark test
1: Do not perform
function
0: 400s (default)
1: 1ms
2: 2ms
0: 1 time (default)
1: 2 times
2: 3 times
7 VARIOUS SETTINGS
7.2 Parameter Settings
7
73