Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 193

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Error history area
■Error history data 1 to 15
The following table shows the configuration of the data and contents stored in each error history data area.
• NZ2GFSS2-32D-S1
Error history data 1
0000H
0001H
0002H
0003H
0004H
0005H
0006H
0007H
0008H
0009H
000AH
000BH
000CH
000DH
000EH
000FH
Values are stored in Error history data 2 to Error history data 15 (address: 0010H to 00EFH) in the same
format as in Error history data 1 (address: 0000H to 000FH).
• NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1, NZ2GFSS2-16DTE-S1
Error history data 1
0A00H
0A01H
0A02H
0A03H
0A04H
0A05H
0A06H
0A07H
0A08H
0A09H
0A0AH
0A0BH
0A0CH
0A0DH
0A0EH
0A0FH
Values are stored in Error history data 2 to Error history data 15 (address: 0A10H to 0AEFH) in the same
format as in Error history data 1 (address: 0A00H to 0A0FH).
Bit position
b15 to b8
Error code
Error classification
Error item number
First two digits of the year
Month
Hour
Second
Error code details 1
Error code details 2
Error code details 3
Error code details 4
Error code details 5
Error code details 6
Error code details 7
System area
Bit position
b15 to b8
Error code
Order of generation
First two digits of the year
Month
Hour
Second
Error code details 1
Error code details 2
Error code details 3
Error code details 4
Error code details 5
Error code details 6
Error code details 7
Error code details 8
System area
b7 to b0
Last two digits of the year
Day
Minute
00H
b7 to b0
Last two digits of the year
Day
Minute
00H
Appendix 4 Remote Buffer Memory