Output Y OFF information clear request
■Device No.
Name
Output Y OFF information clear request
■Description
This remote register area is used to clear Output Y OFF information (RWr1F).
Clear processing continues while the bit of Output Y OFF information clear request (RWw1F) is on.
b15
b14
b13
b12
YF
YE
YD
YC
Off: Output Y OFF information is not cleared.
On: Output Y OFF information is cleared.
For the timing of turning on and off the remote register, refer to the following.
ON
Remote output signal RY0
ON
External output signal Y0
Output Y OFF information Y0
OFF
(RWr1F.b0)
Output Y OFF information
OFF
clear request Y0 (RWw1F.b0)
(1) Remains on even after Y0 turns on.
(2) Turns off when the clear request turns on.
Controlled by the safety remote I/O module
Controlled by the program
b11
b10
b9
b8
YB
YA
Y9
Y8
ON
OFF
ON
OFF
OFF
ON
(1)
Device No.
RWw1F
b7
b6
b5
b4
Y7
Y6
Y5
Y4
ON
b3
b2
b1
b0
Y3
Y2
Y1
Y0
(2)