MAINTENANCE AND INSPECTION
This chapter describes the maintenance and inspection of the safety remote I/O module.
Read [Startup and Maintenance Precautions] in the safety precautions carefully before performing the
inspection, and observe the precautions.
9.1

Daily Inspection

The following table lists the items that must be inspected on a daily basis.
Item
Inspection item
1
Mounting status
Rattling
on a DIN rail
Terminal block
Looseness and
mounting screw
rattling
Terminal block
Attachment of dirt
condition
and foreign
matters
2
Connection
Clearance
status
between
solderless
terminals
3
LED status at
PW LED
power-on or
reset
RUN LED
MODE LED
D LINK LED
SAFETY LED
ERR. LED
I/O PW LED
Input status
indicator LED
Output status
indicator LED
Inspection method
Check for a rattling noise of the
safety remote I/O module.
Check for the looseness of terminal
block mounting screws.
Check for attachment of dirt and
foreign matters.
Check the clearance between
solderless terminals.
Check that the LED is on.
Check that the LED is on for a
moment.
Check that the LED is on for a
moment.
Check that the LED is on for a
moment.
Check that the LED is on for a
moment.
Check that the LED is on for a
moment.
*1
Check that the LED is on for a
moment.
Check that the LED is on for a
*2
moment.
Check that the LED is on for a
*2
moment.
Judgment criterion
Corrective action
The safety remote I/O
Remount the safety remote I/O
module does not rattle.
module on the DIN rail securely.
The terminal block
Retighten terminal block mounting
mounting screws must not
screws securely.
be loose.
Dirt and foreign matters
Remove the terminal block and clean
must not be attached to
it.
terminal blocks.
The proper clearance must
Provide the proper clearance.
be provided between
solderless terminals.
On
Refer to the following and take
corrective actions.
Page 123 Checking the LEDs
On
Replace the module with a new one.
(When an LED fails)
On
On
On
On
The LED must be on when
the external power supply is
*3
applied
.
On
On
9 MAINTENANCE AND INSPECTION